Faults, causes and remedies
Code
Warning
Additional information
about causes and rem-
edy:
Analogue input func-
tions impaired.
563
Sensor value missing
2)
from BMS
(building
management system).
Additional information
about causes and rem-
edy:
Control functions im-
paired. A replacement
function is active.
564
Setpoint missing from
2)
BMS
.
Additional information
about causes and rem-
edy:
Control functions im-
paired. A replacement
function is active.
565
Signal too strong at
analogue input AI1.
Additional information
about causes and rem-
edy:
The signal is processed
with the maximum
value.
566
Signal too strong at
analogue input AI2.
Additional information
about causes and rem-
edy:
The signal is processed
with the maximum
value.
567
Calibration of Wilo
sensor missing.
Additional information
about causes and rem-
edy:
The pump function is
slightly impaired. The
pump can no longer ac-
curately
determine the volume
flow.
569
Configuration missing.
Cause
Remedy
Sensor source or
Check configuration and
2)
BMS
is configured
function of BMS
incorrectly.
Communication has
failed.
Sensor source or
Check configuration and
2)
BMS
is configured
function of BMS
incorrectly.
Communication has
failed.
The available signal is
Check input signal.
significantly over the
expected maximum.
The available signal is
Check input signal.
significantly over the
expected maximum.
Concurrent replace-
Replacement of a compo-
ment of electronic
nent, short commissioning
module and sensor
and fresh replacement
with spare parts.
with the spare part.
Pump configuration is
Configure pump. Software
missing.
update is recommended.
2)
.
2)
.