Electrical connection
Connection
Terminal cross-sec-
tion
in mm
Min.
Electrical mains connec-
≤ 4 kW:
tion
4x1.5
> 4 kW:
4x2.5
SSM
2x0.2
SBM
2x0.2
Digital input EXT. OFF
2x0.2
Digital input EXT. MIN/
2x0.2
EXT. MAX
Analogue input 1
2x0.2
Analogue input 2
2x0.2
Analogue input 3
2x0.2
Analogue input 4
2x0.2
Wilo Net
3x0.2
CIF module
3x0.2
Table 10: Cable requirements
*
Cable length ≥ 2 m: use shielded cables.
**
When using ferrules, the maximum cross-section at the terminals of the communica-
tion interfaces is reduced to 0.25 ... 1 mm².
In order to comply with electromagnetic compatibility standards, the following cables
must always be shielded:
ƒ
Cable for EXT. OFF/MIN/MAX at digital inputs
ƒ
Temperature sensors at analogue inputs
ƒ
External control cable sensors at analogue inputs
ƒ
Differential pressure sensor (DPS) at analogue inputs, if installed on-site
ƒ
Twin-head pump cable with two single pumps in the Y-piece (bus communication)
ƒ
CIF module to the building automation (bus communication)
The shield is connected to the cable bushing on the electronic module. See Fig. 24.
Terminal connections
Terminal connections for all cable connections in the electronic module correspond to
push-in technology. They can be opened with a screwdriver type slot SFZ 1 –
 0.6 x 0.6 mm. Exception: Wilo-Smart Connect Module BT.
Length of cable to strip
The stripping length of the cables for the terminal connection is 8.5 mm ... 9.5 mm.
Terminal cross-sec-
tion
2
2
in mm
Max.
≤ 4 kW:
4x4
> 4 kW:
4x6
3x1.5 (1.0**)
changeover relay
3x1.5 (1.0**)
changeover relay
2x1.5 (1.0**)
2x1.5 (1.0**)
2x1.5 (1.0**)
2x1.5 (1.0**)
2x1.5 (1.0**)
2x1.5 (1.0**)
3x1.5 (1.0**)
3x1.5 (1.0**)
Cable
*
*
*
*
*
*
*
*
Shielded
Shielded
WILO SE 2021-12