Setting The Control Functions - Wilo Stratos GIGA2.0-I Notice De Montage Et De Mise En Service

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Installation and operating instructions Wilo-Stratos GIGA2.0-I, Wilo-Stratos GIGA2.0-D
Commissioning
There are three different classes of status displays.
1.
Display process:
on-going processes have been highlighted in blue.
Processes mean pump operation may deviate from the adjusted control.
Example: software update.
2.
Display warning:
warning messages have been highlighted in yellow.
The pump functions are restricted if a warning has been output (see "Warning
messages" [} 249] section).
Example: cable break detection on analogue input.
3.
Display error:
error messages have been highlighted in red.
The pump stops operation if an error has occurred (see "Error messages" [} 247]
section).
Example: ambient temperature too high.
Further status displays, if available, can be displayed by turning the operating button to
the corresponding symbol.
Symbol
Meaning
Error message
Pump stopped!
Warning message
Pump operation restricted!
Communication status – a CIF module has been installed and is act-
ive.
Pump in control mode, monitoring and control by building auto-
mation available.
Software update started – transfer and verification
Pump continues to run in control mode until the update bundle
has been fully transferred and verified.
Table 18: Potential data displayed in the status area
Additional settings can be made in the "Context" menu, if necessary. For this purpose,
press the "Context" button
Press the "Back" button
to return to the main menu.
NOTICE
A set control mode is interrupted when a process is running. The pump starts to run
in the set control mode once the process is ended.
NOTICE
Repeatedly pressing or pressing and holding the "Back" button after an error mes-
sage has occurred will open the "Error" status display and not take you back to the
main menu.
The status area is highlighted in red.
.