Communication interfaces: Setting and function
For the transfer of analogue signal values to setpoints, only the transfer ramp is now
defined. For this purpose, the minimum and maximum support points of the character-
istic curve are specified and the respective setpoints are amended (MIN signal/value as-
signment and MAX signal/value assignment).
Min signal/value assignment
Analogue input (AI2)
Signal value
Corresponding value
Fig. 80: Minimum signal/value assignment
Max signal/value assignment
Analogue input (AI2)
Signal value
Corresponding value
Fig. 81: Max. signal/value assignment
When all signal/value assignments have been performed, the setting of the analogue
setpoint source is completed.
An editor for adjusting the substitute setpoint in the event of a cable break or wrong
configuration of the analogue input will open.
...►
Set input for external setpoint
Select setpoint source
Current source: Analogue input 2
Set setpoint source
Setpoint sensor: 4 – 20 mA
Substitute setpoint in the event of a cable break
Current: 6.0 m
Fig. 82: Substitute setpoint in the event of a cable break
Set minimum point
of setpoint pump curve
of delivery head
for Δp-v.
Set maximum point
of setpoint pump curve
of delivery head
for Δp-v.
If a
cable break at the
external setpoint source
is detected, this substitute value is
used
as the setpoint.