14.5

Device information

14.6

Pump kick

15
Diagnostics and measured val-
ues
Installation and operating instructions Wilo-Stratos GIGA2.0-I, Wilo-Stratos GIGA2.0-D

Diagnostics and measured values

Under "Settings"
1.
"Device settings"
2.
"Device information"
you can read information about product names, the product and serial number as
well as software and hardware version.
In order to prevent blocking of the pump, a pump kick is set on the pump. After a set
time interval, the pump starts and switches off after a short time.
Prerequisite:
for the pump kick function, the mains voltage must not be interrupted.
CAUTION
Blockage of the pump due to long downtimes!
Long downtimes may lead to blockage of the pump. Do not deactivate pump kick!
Pumps switched off through remote operation, bus command, control input External
OFF or 0 ... 10 V signal run for a short time. This prevents blockage after long down-
times.
In the "Settings" menu 
, select
1.
"Device settings"
2.
"Pump kick"
ƒ
The time interval for the pump kick can be set between 2 and 72 hours (factory
setting: 24 h).
ƒ
The pump kick can be switched on and off.
NOTICE
When it is planned to switch off the mains voltage for a longer period of time, the
pump kick must be performed using an external control by switching on the mains
voltage briefly.
For this purpose, the pump must be switched on by the controller before the power
supply is interrupted.
In order to support fault analysis, the pump provides additional help apart from fault
notifications.
Diagnostics help is used for diagnosis and maintenance of electronics and interfaces.
Apart from hydraulic and electrical overviews, information about interfaces, device in-
formation and manufacturer's contact data are provided.
Diagnostics and measured values
Diagnostics help
Pump and interface test
Heat/cooling quantity measuring
Current: switched off
Operating data, statistics
Display of measured data
Maintenance
Basic functions, ...
Fig. 90: Diagnostics and measured values