Installation and operating instructions Wilo-Stratos GIGA2.0-I, Wilo-Stratos GIGA2.0-D
Communication interfaces: Setting and function
Optional cable break detection
Analogue input (AI2)
Switched off
Switched on
Limit value
Fig. 77: Cable break limit value
Define limit value for cable break by turning the operating button and confirm by
pressing it.
In the next step define whether
ƒ
the analogue signal only changes the setpoint
ƒ
and the pump is additionally switched off through the analogue signal.
A setpoint change can be done through analogue signals without switching on and off
the pump through the signals. In this case, "Switched off" is selected.
If the "On/off by analogue signal" function is switched on, the limit values must be
defined for the switch on/off.
Subsequently assign the MIN signal/value and MAX signal/value.
ON/OFF through analogue signal
Analogue input (AI2)
Switched off
Switched on
Fig. 78: On/off through analogue signal
Limit values for ON/OFF
Analogue input (AI2)
Limit value OFF
Switched on
Limit value ON
Fig. 79: Limit values for ON/OFF control through analogue signal
en
Signal strength below
the set limit value
is interpreted as
a cable break.
The analogue signal
changes the setpoint and
switches the pump ON
or OFF
via a limit value.
The analogue signal
changes the setpoint and
switches the pump ON
or OFF
via these limit values.
227