Fig. 18: Threaded cable glands/cable bushings
Installation and operating instructions Wilo-Stratos GIGA2.0-I, Wilo-Stratos GIGA2.0-D
Electrical connection
Connection
Electrical mains connection
3~380 V AC ...
3~440 V AC
SSM
1~220 V AC ...
1~240 V AC
12 V DC
SBM
1~220 V AC ...
1~240 V AC
12 V DC
Digital input EXT. OFF
(24 V DC)
Digital input EXT. MAX/EXT.
MIN
(24 V DC)
Bus Wilo Net
(Bus communication)
Analogue input 1
0 ... 10 V, 2 ... 10 V,
0 ... 20 mA, 4 ... 20 mA
Analogue input 2
0 ... 10 V, 2 ... 10 V,
0 ... 20 mA, 4 ... 20 mA
Analogue input 3
PT1000
0 ... 10 V, 2 ... 10 V,
0 ... 20 mA, 4 ... 20 mA
Analogue input 4
PT1000
0 ... 10 V, 2 ... 10 V,
0 ... 20 mA, 4 ... 20 mA
CIF module
(Bus communication)
Electrical connection of the
fan
assembled at the factory
(24 V DC)
Table 9: Cable connections
Cable requirements
Terminals are intended for rigid and flexible conductors with or without ferrules.
If flexible cables are used, the use of ferrules is recommended.
Threaded cable gland
Plastic
Plastic
Plastic
Metal with shielding
Metal with shielding
Metal with shielding
Metal with shielding
Metal with shielding
Metal with shielding
Metal with shielding
Metal with shielding
en
Cable
Terminal
bushing
no.
Fig. 18,
Item
1
1 (Fig. 19)
2
2 (Fig. 19)
3
3 (Fig. 19)
4, 5, 6
11 ... 14
(Fig. 20)
(DI1 or DI2)
4, 5, 6
11 ... 14
(Fig. 20)
(DI1 or DI2)
4, 5, 6
15 ... 17
(Fig. 20)
4, 5, 6
1, 2, 3
(Fig. 20)
4, 5, 6
4, 5
(Fig. 20)
4, 5, 6
6, 7, 8
(Fig. 20)
4, 5, 6
9, 10
(Fig. 20)
4, 5, 6
4 (Fig. 25)
7
4 (Fig. 19)