Désignation - Wilo Stratos GIGA2.0-I Notice De Montage Et De Mise En Service

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Notice de montage et de mise en service Wilo-Stratos GIGA2.0-I, Wilo-Stratos GIGA2.0-D
Raccordement électrique
Affectation des bornes
Désignation
Affectation
Analogique IN (AI1)
+ 24 V (borne : 1)
(Fig. 20)
+ In 1 → (borne : 2)
- GND (borne : 3)
Analogique IN (AI2)
+ In 2 → (borne : 4)
(Fig. 20)
- GND (borne : 5)
Analogique IN (AI3)
+ 24 V (borne : 6)
(Fig. 20)
+ In 3 → (borne : 7)
- GND (borne : 8)
Analogique IN (AI4)
+ In 4 → (borne : 9)
(Fig. 20)
- GND (borne : 10)
Numérique IN (DI1)
DI1 → (borne : 11)
(Fig. 20)
+ 24 V (borne : 12)
Numérique IN (DI2)
DI2 → (borne : 13)
(Fig. 20)
+ 24 V (borne : 14)
Wilo Net
↔ H (borne : 15)
(Fig. 20)
↔ L (borne : 16)
GND H/L (borne : 17)
SSM
COM (borne : 18)
(Fig. 23)
← NO (borne : 19)
← NC (borne : 20)
SBM
COM (borne : 21)
(Fig. 23)
← NO (borne : 22)
← NC (borne : 23)
Alimentation réseau
Tabl. 11: Affectation des bornes
AVIS
Nature du signal :
• 0 ... 10 V
• 2 ... 10 V
• 0 ... 20 mA
• 4 ... 20 mA
Résistance au claquage:
30 V CC / 24 V CA
Alimentation électrique :
24 V CC : maximum 50 mA
Nature du signal :
• 0 ... 10 V
• 2 ... 10 V
• 0 ... 20 mA
• 4 ... 20 mA
• PT1000
Résistance au claquage:
30 V CC / 24 V CA
Alimentation électrique :
24 V CC : maximum 50 mA
Entrées numériques pour
contacts secs :
• Tension maximale :
< 30 V CC / 24 V CA
• Courant de boucle maximal :
< 5 mA
• Tension de service : 24 V CC
• Courant de boucle de service :
 2 mA par entrée
Inverseur à contact sec
Charge de contact :
• Minimum admis :
SELV 12 V CA / CC, 10 mA
• Maximum admis : 250 V AC, 1 A,
30 V DC, 1 A
Inverseur à contact sec
Charge de contact :
• Minimum admis :
SELV 12 V CA / CC, 10 mA
• Maximum admis : 250 V AC, 1 A,
30 V DC, 1 A