Signal sources for ZSW1 (positioning mode, r0108.4 = 1)
Signal
Meaning
ZSW1.0
1 = Ready to power-up
ZSW1.1
1 = Ready to operate (DC link loaded, pulses blocked)
ZSW1.2
1 = Operation enabled (drive follows n_set)
ZSW1.3
1 = Fault present
ZSW1.4
1 = No coast down active (OFF2 inactive)
ZSW1.5
1 = No fast stop active (OFF3 inactive)
ZSW1.6
1 = Power-on inhibit active
ZSW1.7
1 = Alarm present
ZSW1.8
1 = Following error within tolerance
ZSW1.9
1 = Control requested
ZSW1.10
1 = Target position reached
ZSW1.11
1 = Home position set
ZSW1.12
= Acknowledgement traversing block activated
ZSW1.13
1 = Drive at standstill
ZSW1.14
Reserved
ZSW1.15
Reserved
<1> Used in telegram 7, 110, 999.
<2> The status word is generated using the binector-connector converter p2088[0].
1
2
DO: SERVO, VECTOR
PROFIBUS - ZSW1 status word 1 interconnection (r0108.4 = 1)
Interconnection
p2080[0] = r0899.0
p2080[1] = r0899.1
p2080[2] = r0899.2
p2080[3] = r2139.3
p2080[4] = r0899.4
p2080[5] = r0899.5
p2080[6] = r0899.6
p2080[7] = r2139.7
p2080[8] = r2684.8
<3>
p2080[9] = r0899.9
p2080[10] = r2684.10
p2080[11] = r2684.11
p2080[12] = r2684.12
p2080[13] = r2199.0
<3> The master system requests the process data.
3
4
[Function diagram]
[Function diagram]
parameters
Internal status word
signal source
[2503.7]
[2610]
[2503.7]
[2610]
[2503.7]
[2610]
[2548.7]
[8060]
[2503.7]
[2610]
[2503.7]
[2610]
[2503.7]
[2610]
[2548.7]
[8065]
[3646.7]
[4025]
[2503.7]
[2503]
[3646.7]
[4020] [3625]
[3646.7]
[3612] [3614]
[3646.7]
[3616] [3620]
[2537.7]
[8010] [3625]
-
-
-
-
5
6
fp_2479_01_eng.vsd
24.01.06 V02.04.00
PROFIBUS sampling time
<1>
Refer to [1020.7]
Inverted
<2>
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
7
8
Function diagram
- 2479 -
SINAMICS S