U_line supply calculated
[8950.4]
300 ms
Nominal line
Calculated
supply voltage
actual line
supply voltage
U_line supply after filter
<1> For p3400.0 = 1 the following applies [8864].
1
2
DO: A_INF
Active infeed - signals and monitoring functions, line supply voltage monitoring (p3400.0 = 0)
Supply voltage
p0210
p0281 (110 %)
A06301 "Line supply overvoltage"
p0282 (85 %)
&
A06105 "Line supply undervoltage"
p0283 (75 %)
F06100 "Shutdown due to line supply undervoltage"
85 % 110 %
A06310 "Supply voltage (p0210) incorrectly parameterized"
[8960.6]
3
4
Monitoring when switching-in the pulses
(regarding the frequency, refer to [8964])
U_line supply after filter
[8960.2]
Vdc_max stat
[8940.4]
5
6
Function diagram
fp_8960_01_eng.vsd
SINAMICS S
13.05.05 V02.04.00
p0115[3] (2000.00 µs)
<1>
A06300
"Line supply voltage too high when powering-up"
--> voltage cannot be controlled
7
8
- 8960 -