Tec_ctrl mop config
0000...0111
p2230[D] (0110)
Data save active
<3>
Initial rounding-off active
Non-volatile data save active
Tec_ctrl mop raise
p2235[C]
(0)
Tec_ctrl mop lower
p2236[C]
(0)
Tec_ctrl mop max
-200.00...200.00 [%]
p2237[D] (100.00)
Tec_ctrl mop min
-200.00...200.00 [%]
p2238[D] (-100.00)
<1>
For p2230.0 = 0, this setpoint is entered after ON.
<2>
If the initial rounding-off is active (p2230.2 = 1), the selected ramp-up and ramp-down times are appropriately exceeded.
<3>
The following prerequisites must be fulfilled in order to be able to save the setpoint in a non-volatile fashion:
- Firmware with V2.3 or higher.
- Control Unit 320 (CU320) with hardware version C or higher (module with NVRAM).
<101> Pre-assignment of the sampling times in p0115, refer to p0112.
1
2
DO: SERVO, VECTOR
Technology controller – motorized potentiometer (r0108.16 = 1)
0
The setpoint for the motorized potentiometer is not saved and after ON is entered using p2240.
1
The setpoint for the motorized potentiometer is saved after OFF and after ON is entered using r2231.
0
Without initial rounding.
1
With initial rounding. The ramp-up/down time set is exceeded accordingly.
0
Non-volatile data save not activated
1
The setpoint for the motorized potentiometer is saved in a non-volatile fashion (for p2230.0 = 1)
Old value is kept
0 0
Tec_ctrl mop before RFG
0 1
r2245
1 0
1 1
1 = OFF1, enable missing
[2634.0]
3
4
<2>
<2>
Tec_ctrl mop t_up
Tec_ctrl mop t_down
0.0...1000.0 s
0.0...1000.0 s
p2248[D] (10.0)
p2247[D] (10.0)
y
p2237
x
x
-p2238
y = 0
Tec_ctrl mop start
r0046.0
-200.00...200.00 %
p2240[D] (0.00)
<1>
Tec_ctrl mop SP
r2231
5
6
Function diagram
fp_7954_01_eng.vsd
SINAMICS S
04.08.05 V02.04.00
4000.00 µs
Refer to [1020.7]
<101>
Tec_ctrl mop after RFG
y
r2250
7
8
- 7954 -