<1> In order to maintain the PROFIdrive profile, receive word 1 must be used as control word (STW1) (due to bit 10 "control requested").
<2> Using the connector-binector converters, the bits can be extracted from two of the PZD receive words 5 to 16 and used as binectors.
<3> For words and double words, the representation 4000 hex = 100 % or 4000 0000 hex = 100 % for double words.
Reference quantities p200x are decisive for the ongoing interconnection (100 % corresponds to p200x).
For temperatures, the following applies: 100 degrees Celsius corresponds to 100 % = 4000 hex or 4000 000 hex, and 0 degrees Celsius corresponds to 0 %.
The following applies to the electrical angle: 90 degrees corresponds to 100 % = 4000 hex or 4000 0000 hex, and 0 degrees corresponds to 0 %.