Siemens SINAMICS S Manuel page 1131

Table des Matières

Publicité

<1>
M_max upper/mot
-100 000.00...100 000.00 Nm
p1520[D] (100.00)
M
M_max upper/mot scal
-2000.0...2000.0 %
2
1
n
p1524 (100.0)
Example:
0 = Fast stop active
(OFF3)
r0899.5
<1>
M_max lower/regen
-100 000.00...100 000.00 Nm
p1521[D] (-100.00)
M_max upper/regen scal
-2000.0...2000.0 %
M
p1525 (100.0)
n
3
4
<1> For p1400.4 = 0 the torque limits for the positive and negative torque direction (upwards and downwards) are compatible to MASTERDRIVES and MICROMASTER 4.
"Normal case": If neither dynamic limits nor offset are required, the upper torque limit is entered via p1520 and the lower (as negative value) via p1521.
<2> Danger!
Negative values at
or positive values at
A
<3> The limiters ensure that the limits do not mutually "overtake" one another.
<4> For the manufacturer-specific PROFIBUS telegrams 102 ... 106 r1543 is switched-in here [5610.4].
1
2
DO: SERVO
Servo torque limits - upper/lower torque limit
Upper torque limit
M_ upper/mot
p1522[C]
p1520[D]
(1520)
M_max up/mot scal
p1528[C]
p1524[D]
(1524)
e.g. from MOMRED
<4>
M_lim var/fixed S_src
p1551[C]
(1)
Lower torque limit
M_max lower/regen
p1523[C]
p1521[D]
(1521)
M_max low/regen scal
p1529[C]
p1525[D]
(1525)
e.g. from MOMRED
<4>
B
represent a minimum torque for the other torque direction and can cause the motor to accelerate uncontrollably.
Fault F07090 is initiated, which can also be disabled.
With
A
<
B
3
4
<2>
A
M_max upper without offs
0
1
<2>
<3>
<2>
1
0
M_max lower without offs
B
<2>
5
fp_5630_01_eng.vsd
21.12.05 V02.04.00
r1526
M_max upper total
M_max Offset
r1534
+
[5640.1]
+
M_max offset
-100 000.00...100 000.00 Nm
p1532[D] (0.00)
F07090
+
M_max lower total
M_max offset
r1535
+
[5640.1]
r1527
M
p1520
{p1522}
{p1523}
p1521
6
7
Function diagram
SINAMICS S
1000.00 µs
p1532
8
- 5630 -