Temperature sensor
+ temp
2 mA
X520.5
+
X520.6
-
KTY/PTC
- temp
<1> p3665
= 0: No sensor
= 1: PTC
= 2: KTY
<2> A fault or alarm in the temperature evaluation of the VSM is communicated to the downstream evaluation using special temperature values.
<3> As a result of the wire breakage monitoring the maximum temperature that can be measured is limited to approx. 175 °C.
<4> A value > 250 °C de-activates the alarm or fault.
<5> Can only be used in conjunction with chassis infeeds.
1
2
DO: A_INF
Voltage Sensing Module (VSM) - temperature evaluation
Sensor type
p3665 (0)
Hardware
<1>
smoothing 1 s
A
Resistance
calculation
D
Overtemperature hysteresis
<2>
Alarm A35920
temperature sensor evaluation
Alarm is not present
Alarm is present
-300 °C
3
4
R
KTY
Software smoothing 0.5 s
PTC
PTC resistor
threshold 1650 Ohm
Overtemperature alarm threshold
0...301 °C
<4>
p3667[0] (150)
1
0
p3669
1
0
<4>
Overtemperature fault threshold
0...301 °C
p3668[1] (180)
5
6
fp_9886_01_eng.vsd
07.12.04 V02.04.00
4000.00 µs
248 °C
<3>
<5>
Sensor type
T
p3665 (0)
-140 °C
<1>
2
1
1
0
0
-50 °C
250 °C
1
Sensor resistance
[9887.1]
A34211
"Temperature alarm threshold exceeded"
r3664.0
F34207
"Temperature fault threshold exceeded"
r3664.1
Temperature KTY
r3666
7
8
Function diagram