Signal sources for ZSW1 (Interface Mode SIMODRIVE 611 universal, p2038 = 1)
Signal
Meaning
ZSW1.0
1 = Ready to power-up
ZSW1.1
1 = Ready to operate (DC link loaded, pulses blocked)
ZSW1.2
1 = Operation enabled (drive follows n_set)
ZSW1.3
1 = Fault present
ZSW1.4
1 = No coast down active
ZSW1.5
1 = No fast stop active
ZSW1.6
1 = Power-on inhibit active
ZSW1.7
1 = Alarm present
ZSW1.8
1 = Speed setpoint - actual value deviation within tolerance t_off
ZSW1.9
1 = Control requested
<2>
ZSW1.10
1 = f or n comparison value reached/exceeded
ZSW1.11
Reserved
ZSW1.12
Reserved
ZSW1.13
Reserved
ZSW1.14
1 = Closed-loop torque control active
ZSW1.15
Reserved
<1> Used in telegrams 1, 2, 3, 4, 5, 6, 102, 103, 105, 106, 116, 352.
<2> The master system requests the process data.
1
2
DO: SERVO
PROFIBUS - ZSW1 status word interconnection (p2038 = 1)
Interconnection
parameters
p2080[0] = r0899.0
p2080[1] = r0899.1
p2080[2] = r0899.2
p2080[3] = r2139.3
p2080[4] = r0899.4
p2080[5] = r0899.5
p2080[6] = r0899.6
p2080[7] = r2139.7
p2080[8] = r2197.7
p2080[9] = r0899.9
p2080[10] = r2199.1
p2080[14] = r1407.2
3
4
[Function diagram]
[Function diagram]
Internal status word
Signal source
[2503.7]
[2610]
[2503.7]
[2610]
[2503.7]
[2610]
[2548.7]
[8060]
[2503.7]
[2610]
[2503.7]
[2610]
[2503.7]
[2610]
[2548.7]
[8065]
[2534.7]
[8010]
[2503.7]
[2503]
[2536.7]
[8010]
-
-
-
-
-
-
-
-
-
[2522.7]
[2522]
-
-
-
5
6
Function diagram
fp_2453_01_eng.vsd
SINAMICS S
20.03.06 V02.04.00
PROFIBUS sampling time
<1>
Refer to [1020.7]
Inverted
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
7
8
- 2453 -