Changing the fault response for maximum 20 faults <1>
p2100
[0]
0. Fault code
[0]
[1]
1. Fault code
[1]
[19]
19. Fault code
[19]
Changing the acknowledge mode for maximum 20 faults <1>
p2126
[0]
0. Fault code
[0]
[1]
1. Fault code
[1]
[19]
19. Fault code
[19]
<1> Fault response, acknowledge mode and message type for all faults and alarms are practically pre-set as default in the factory setting.
Changes that may be required are only possible in specific value ranges that SIEMENS has specified.
When the message type is changed, the supplementary information "wanders" from fault value r0949 to the alarm value r2124 and vice versa.
1
2
DO: All objects
Faults and alarms - fault/alarm configuration
p2101
Fault response
0 = NONE
Fault response
1 = OFF1
2 = OFF2
3 = OFF3
4 = STOP1
5 = STOP2
6 = DCBRK
7 = Encoder
Fault response
p2127
Acknowledge mode
1 = Acknowledgment is only possible using POWER ON
Acknowledge mode
2 = Acknowledgment IMMEDIATELY after the cause has been removed.
3 = Acknowledge only when the PULSES ARE INHIBITED.
Acknowledge mode
3
4
Changing the message type - fault <==> alarm for maximum 20 faults/alarms <1>
p2118
[0]
0. Fault/alarm code
[1]
1. Fault/alarm code
[19]
19. Fault/alarm code
5
6
fp_8075_01_eng.vsd
06.03.06 V02.04.00
Background
Refer to [1020.7]
p2119
[0]
Fault/alarm type
1 = Fault
[1]
Fault/alarm type
2 = Alarm
3 = No message
[19]
Fault/alarm type
7
8
Function diagram
- 8075 -
SINAMICS S