Dis T.1634007e
SENSORS-ENABLE / DISABLE (Level 1):
These two items allow you to enable or disable one or more sensors, even simultaneously.
A disabled sensor is displayed on the main screen, with "
The Disabled sensors will no longer activate the fault and alarm outputs (relays)
associated with them and therefore the devices connected to the relays will not be
activated. This function can be used to exclude Sensors, not yet installed, in failure, be
removed for repair or for a short time during maintenance, in order to avoid activating
the alarms and then block a plant not yet put into safety.
To enable or disable a sensor press
highlighted. With
and
on a single sensor or on a group of sensors.
The first line, is acting on a single sensor. Pressing
highlight the number of the sensor. Then you choose the desired
number, with
and
confirmation window will appear.
nd
The 2
line, acts on a group of sensors. Pressing
st
will highlight the 1
sensor's number of the group.
If the two sensor numbers are the same, the effect is identical to the
management of the single sensor.
With
and
, you can choose the number of required sensor,
pressing
and
pressing
again, confirmation window will appear.
ENTER
Press
to confirm, or to go back, press
ENTER
the group's sensors is not configured, a window notifies you that the
operation is not possible.
Then the screen returns to the selection of the sensor.
If you have selected a group of sensors, the ones that have been configured are enabled or
disable.
If the procedure is correct, a window warns that the operation has been
successful. Then the screen returns to the start of the Enable / Disable
management
IMPORTANT: Before starting the setup, decide how many and which outputs are
to be used (relay) according to the type, to the requested operation and the
number of actuators installed and in which the alarm levels are associated.
CONFIGURE SENSORS (Level 2):
here are two ways to configure a sensor, but both can be configured
only of our production models
that have some parameters not editable and others already preset, but it
all changed, must be entered only the outputs (relay number) you
want to activate.
The first way allows you to select, manually, one at a time sensor,
including ones that are preconfigured.
The second way allows you can manually enter all the parameters,
which are freely editable. This allows you to use compatible products
but not of our production or new models not yet included in the list of
pre-configured ones.
For safety, it is not allowed to set outputs separately. They can only be configured in
CONFIGURE or MODIFY a Sensor, a Logic Input or a Zone.
TECNOCONTROL S.r.l. - Via Miglioli, 47 20054 SEGRATE (MI) - Tel. 02. 26 92 28 90 - Fax 02. 21 33 734
CE424P User manual
key on the relevant item
it is possible to select, if you take action
keys and then, pressing
you change from one value to another, then
(TABLES List detectors
".
st
on the 1
, will
the
nd
on the 2
line,
. If the sensor or one of
PRECONFIGURED)
Pag. 22/52
ENABLE
SENSOR N.
FROM N.
TO N.
ENABLE
SENSOR N.
FROM N.
TO N.
CONFIRM ?
YES = ENTER
NO = ESC
SENSOR
N. 1
NOT CONF.
SENSOR
N. 1
ENABLE
SENSORS CONFIG.
1 PRECONF. SENS.
2 GENERIC SENS.