Dis T.1634007e
CONFIGURE - PRECONFIGURED SENSOR:
To start the configuration press
With
or
and then pressing
the sensor to be configured.
For safety, if you choose a previously configured sensor,
the screen that warns of the possible error, with you can
confirm with
ENTER
new sensor, instead of pressing
operation and you can choose another sensor.
The configuration of a dual sensor (TS255), uses 2 consecutive sensors (1-2, 3-4, or 2-3,
4-5 etc.) You should always start from the first configuration of the two.
Next, you can choose the model code.
To choose the desired one, its structure must be followed as described
below, first the first 2 letters must be chosen, then the 3 numbers and
then the other letters (if present) until the complete code of the model is
composed.
CODE STRUCTURE: our codes are made up of 2 letters that identify the type of product (e.g.
TS = signal transmitter), 3 numbers that identify some functional characteristics, (e.g. TS2xx =
digital signal output), other 2 or more letters specify the type of sensing element used and the
gas detected, e.g. TS282KM (K=catalytic and M = Methane), other letters or numbers, if
present, indicate other specific characteristics of the product.
With
and
you can scroll between the groups of letters and
numbers that make up the model, with
and move on. With
ESC
Example: for model TS282KM, first select TS and confirm by pressing
. Then select the 2
ENTER
complete the selection by selecting the complete entry TS282KM and
press
to confirm.
ENTER
Chosen model, will appear a short reminder referring to the
configuration of voices OUTPUT 1, OUTPUT 2 and OUTPUT 3 that
activates the corresponding alarm outputs (relays) and the specific
parameters (delays) that define the operation mode of the relay outputs.
Chosen model, will load its configuration.
With
and
you can scroll through the various items. Press
on the item, it is only highlighted the value, editable with
With
and
you move from one field to the other in the same row
(where applicable). The ETIC item, is explained later. Then by pressing
the change is accepted. With
ENTER
and the entire row is selected, indicating that it is possible to go back to
scrolling through the various items.
After the non-editable items, MODEL, TYPE, GAS, UoM. F.S. and AL. other fields have a
presetted value but can be changed. The only empty fields are OUTPUT 1, 2 and 3 where the
number of the relay that will activate the corresponding alarm level (THRESHOLD 1, 2 and 3)
must be entered.
ATTENTION: it is not mandatory to assign an OUTPUT relay number, but if it is not
entered, alarm will not be activated. Number 0 (zero) indicates that no relay is assigned.
Only the configuration procedure of the two HYSTER.OFF / TIME ON functions is different from
that described above, and must be carried out as explained in the following pages.
TECNOCONTROL S.r.l. - Via Miglioli, 47 20054 SEGRATE (MI) - Tel. 02. 26 92 28 90 - Fax 02. 21 33 734
CE424P User manual
on the relevant highlighted item.
ENTER
you can choose the number of
and continue, configuring it as if it were a
you can confirm your choice
you can go back.
nd
item TS282 and confirm with
the previous value is restored
ESC
PRECONF. SENS.
SENSOR N.
YES= ENTER
will cancel the
NO= ESC
PRECONF. SENS.
SENSOR N.
MODEL:
PRECONF. SENS.
SENSOR N.
MODEL:
PRECONF. SENS.
SENSOR N.
key. Finally
MODEL:
CAUTION: If the number of the
relay will not be inserted, the
alarm will not be activated.
ENTER to exit
PRECONF. SENS.
SENSOR N.
and
.
MODEL:
TAG:
TYPE:
GAS:
UoM:
AL:
Pag. 23/52
1
SENSOR USED
CONTINUE ?
1
TS
1
TS255
TS282
TS293
1
TS282KB
TS282KG
TS282KI
TS282KM
1
TS282KM
Flammable
METHANE
% LFL
INCREASING