Dis T.1634007e
MODELS
Detected Gas
(6)
Allarme
=OSSIGENO
(6)
Alarm
=OXYGEN
(6)
Alarme
=OXYGÈNE
Modificabile
TS593 EO
Modifiable
(6)
Allarme
=DECRESCENTE
(6)
Alarm
=DECREASING
(6)
Alarme
=DÉCROISSANTE
NOTES TO THE TABLES 1 and 2:
(1)
It is not recommended to set pre-alarm levels lower than the value indicated.
(2)
the Alarm for oxygen deficiency is displayed as AL..
(3)
the Alarm for oxygen excess is displayed as AL..
(4)
Product discontinued or no longer in stock.
(5)
N.A. Data Not Available
(6)
indicates the Alarm Type selectable in the sensor configuration. It is preconfigured as OXYGEN but can
be changed to DECREASING , if the excess alarm is not needed.
TABLE 3 - Models with Fixed Sensor (Parking, Heating Plants, Civil installations)
WITH CATALYTIC SENSORS FOR FLAMMABLE GASES
MODELS
SE192 KB
SE193 KB
SE192 KG
SE193 KG
SE192 KI
SE193 KI
SE192 KM
SE193 KM
SE193 PB
SE193 PG
SE193 PI
SE193 PM
WITH ELECTROCHEMICAL SENSORS FOR TOXIC GASES
MODELS
SE192 EC
SE193 EC
NOTE TO TABLE 3: The SE183 models can be configured using the SE193 code and the only
construction difference is the enclosure (Exd) used.
TABLE 4 - Models and Values of TLVs
MODELS
TS293 EA
TS282 EA
TS293 EA-H
TS293 EC-S
TS282 EC-S
TS293 EC-H
TS282 ECL
TS282 EH
TS293 EH
TS282 EHCL
TS282 EHCN TS293 EHCN TS593 EHCN
TS282 EN
TS293 EN
TS282 EN2
TS293 EN2
TS282 ES
TS293 ES
TS282 IC2
TS293 IC2
TS282 IC2-H TS293 IC2-H TS593 IC2-H
TS210 IC2
The values indicated refer to the requirements of the bodies that deal with the health of workers,
the European COSHH (Control Of Substances Hazardous to Health) and the US OSHA (Occupational Safety
and Health Administration). The indicated values may change according to national standards.
TABLE 5A-Pre-configured values for PARKING-EN (EN50545-1)
TECNOCONTROL S.r.l. - Via Miglioli, 47 20054 SEGRATE (MI) - Tel. 02. 26 92 28 90 - Fax 02. 21 33 734
CE424P User manual
RANGE UNIT
/
Configurable
O
0÷25.0
2
Detected Gas RANGE UNIT
Vap.BENZINA
PETROL vapors
Vap.ESSECE
GPL (Butano)
LPG (Butane)
0÷20
IDROGENO
HYDROGEN
METANO
METHANE
Vap.BENZINA
PETROL vapors
Vap.ESSECE
GPL (Butano)
LPG (Butane)
0÷100
IDROGENO
HYDROGEN
METANO
METHANE
Detected Gas RANGE UNIT
CO
0-300
Detected
Gas
TS593 EA
NH
3
TS593 EA-H
TS593 EC-S
CO
TS593 EC-H
CL
2
TS593 EH
H
S
2
HCL
HCN
TS593 EN
NO
TS593 EN2
NO
2
TS593 ES
SO
2
TS593 IC2
CO
2
CO
2
CO
2
Threshold 1(AL1) Threshold 2(AL2) Threshold 3(AL3)
19.5
% vol
20.0
Alarm levels
Threshold 1(AL1) Threshold 2(AL2) Threshold 3(AL3)
(1)
%LFL
7
(1)
%LFL
10
Alarm levels
Threshold 1(AL1) Threshold 2(AL2) Threshold 3(AL3)
ppm
25
Alarm levels
TLV-TWA
RANGE UNIT
Threshold 1
25
(COSHH)/(OSHA)
0-300
ppm
30
(COSHH)
0-300
ppm
0.5
(OSHA)
0-10.0
ppm
5
(COSHH)
0-100
ppm
5.0
(OSHA)
0-10.0
ppm
4.7
(OSHA)
0-10.0
ppm
25
(COSHH)/(OSHA)
0-100
ppm
3.0
(COSHH)
0-30
ppm
2
(COSHH)
0-20.0
ppm
% vol 0.50
(COSHH)/(OSHA)
0-5.00
1000
0-5000
ppm
% vol 0.50
(COSHH)/(OSHA)
0-2.00
Alarm levels
Pag. 45/52
(2)
(3)
18.5
22.5
19.5
18.5
10
20
15
20
50
150
TLV-STEL
TLV-Ceiling
Threshold 2
Threshold 3
35
(COSHH)
50
(OSHA)
200
(COSHH)
250
0.5
(COSHH)
1.0
10
20
(COSHH)
5.0
(COSHH)
10.0
10
4.7
(COSHH)
(OSHA)
25
50
(COSHH)
(OSHA)
5.0
(COSHH)
15.0
5
(COSHH)
10
1.50
3.00
(COSHH)
1500
5000
(COSHH)/(OSHA)
1.50
2.00
(COSHH)