Total current is too high
Every output is supplied with a continuous current of max.
0.5 A. Current loads over 0.5 A per output can lead to limited
system functioning.
Make sure that the current load of 0.5 A per output is not
O
exceeded.
6.3.6
Each output module has its own M12 connection for the load
supply. Each of the 4 outputs are supplied via the load supply.
The U
The connection cable for the output module power supply must
meet the following requirements:
Cable socket: M12×1, 4-pin, A-coded without center hole (to
W
ensure correct plug-in connection).
Cable cross-section: per wire  0.5 mm
W
Length: Max. 20 m
W
Output assignment for 8x output module, DO8_M8,
M8x1 socket
Signal
Not assigned
Ox
GND
Output assignment for 8x output module, DO8_M12,
M12x1 socket, A-coded
Signal
NC
O1, O3, O5 or O7
GND
O0, O2, O4 or O6
NC

Connecting the output module load supply

and U
voltages are galvanically isolated.
Q1
Q2
Assignment
Not connected
Ox output signal
(nominal voltage 24 V)
GND actuator reference
Connected to shield potential
Assignment
Not connected
Output signal
Reference potential
Output signal
Not connected
Connected to shield potential