AVENTICS | CMS, BDC, Stand-Alone | R412008961–BDL–001–AF
Assembly
Table 10:
Pin assignment of the plugs X201, X202,
X203, X204 for R412008692, 4x2 valve
outputs with M8 connection, 3-pin
Pin
Assignment
X204
1
Valve output 8
4
Valve output 7
3
0 V / ground for U
U
of the bus coupler
Q2
1)
Observe the max. total current of the respective bus coupler.
6.5.5 Connection conditions for module
extension R412008694
The external valves are connected via plug X20. The
external voltage supply to the module is connected via
plug X1S.
Use pre-assembled plug connections and cables to
connect the modules.
O
Observe the pin assignment in Tab. 11 and Tab. 12 if
you do not use pre-assembled plug connections and
cables.
Table 11:
Pin assignment of plug X21 for R412008694,
voltage input, M12 socket, A-coded, 4-pin
Pin
Voltage input
1
GND 2
2
U
+1
3
GND 1
4
U
+2
Signal current
Max. 100 mA per
valve solenoid
Max. 100 mA per
valve solenoid
and
Q1
Assignment
First external voltage supply
Second external voltage
supply
1)
1)