Diagnostic Data; Cyclical Diagnostic Data Of The Valve Drivers; Acyclical Diagnostic Data Of The Valve Drivers (Explicit Messages); Parameter Data - Aventics DeviceNet Description Du Système Et Notice D'emploi

Coupleur de bus aes / pilote de distributeur av
Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 137
Table 17:
Valve driver board, 3x
Output byte
Bit 7
Valve designation
Solenoid designation
1)
Bits that are marked with a "–" may not be used and are assigned the value "0".
Table 18:
Valve driver board, 4x
Output byte
Bit 7
Valve designation
Valve 4
Solenoid designation
Sol. 12
AVENTICS | Bus Coupler AES/Valve Driver AV, DeviceNet | R412018138–BAL–001–AC
1)
Bit 6
Bit 5
Valve 3
Sol. 12
Bit 6
Bit 5
Valve 4
Valve 3
Sol. 14
Sol. 12
Tables 16–18 refer to double solenoid valves. With a single solenoid valve, only solenoid 14 is
used (bits 0, 2, 4, and 6).
6.2

Diagnostic data

6.2.1

Cyclical diagnostic data of the valve drivers

The valve driver sends the diagnostic message with the input data to the bus coupler (see Table 14).
The diagnostic bit for the corresponding module (module number) indicates where the fault
occurred. The diagnostic message consists of a diagnostic bit, which is set in the event of a short
circuit of an output (group diagnostics).
The diagnostic bit can be read as follows:
Bit = 1: An error has occurred.
Bit = 0: No error has occurred.
6.2.2

Acyclical diagnostic data of the valve drivers (explicit messages)

The diagnostic data of the valve drivers can be read out as follows:
Enter the following values in the PLC configuration software in the corresponding input field.
Table 19:
Reading out the diagnostic data of the modules
Field name in the software window
Class
Instance
Attribute
You will receive 1 data byte as a response. This byte contains the following information:
Byte 1 = 0x00: No error has occurred.
Byte 1 = 0x80: An error has occurred.
6.3

Parameter data

The valve driver board does not contain any parameters.
Bit 4
Bit 3
Valve 3
Valve 2
Sol. 14
Sol. 12
Bit 4
Bit 3
Valve 3
Valve 2
Sol. 14
Sol. 12
Value in input field
0x64
Module number in hexadecimal coding
(e.g. module no. 18 = 0x12)
0x03
Structure of the Valve Driver Data
Bit 2
Bit 1
Valve 2
Valve 1
Sol. 14
Sol. 12
Bit 2
Bit 1
Valve 2
Valve 1
Sol. 14
Sol. 12
95
Bit 0
Valve 1
Sol. 14
Bit 0
Valve 1
Sol. 14

Publicité

Table des Matières
loading

Table des Matières