5.6

Bus coupler diagnostic data

The diagnostic data can be turned on or off on the DIP switch DR.3. When delivered the diagnostics
are turned off.
5.6.1

Structure of the diagnostic data

When diagnosis is activated, the bus coupler sends 8 bytes of diagnostic data, which are appended
to the input data of the modules. A valve system consisting of a bus coupler and a module with
2 bytes of input data thus has a total of 10 bytes of input data. A valve system consisting of a bus
coupler and a module without input data has a total of 8 bytes of input data.
The 8 bytes of diagnostic data contain
2 bytes of diagnostic data for the bus coupler and
6 bytes of group diagnostic data for the modules.
The diagnostic data is organized as shown in Table 14.
Table 14:
Diagnostic data appended to input data
Byte no.
Bit no.
Meaning
Byte 0
Bit 0
Actuator voltage UA < 21.6 V (UA-ON)
Bit 1
Actuator voltage UA < UA-OFF
Bit 2
Electronics power supply < 18 V
Bit 3
Electronics power supply < 10 V
Bit 4
Reserved
Bit 5
Reserved
Bit 6
Reserved
Bit 7
Reserved
Byte 1
Bit 0
The backplane of the valve zone issues a warning.
Bit 1
The backplane of the valve zone issues an error.
Bit 2
The backplane of the valve zone attempts
a re-initialization.
Bit 3
Reserved
Bit 4
The backplane of the I/O zone issues a warning.
Bit 5
The backplane of the I/O zone issues an error.
Bit 6
The backplane of the I/O zone attempts
a re-initialization.
Bit 7
Reserved
Byte 2
Bit 0
Group diagnosis, module 1
Bit 1
Group diagnosis, module 2
Bit 2
Group diagnosis, module 3
Bit 3
Group diagnosis, module 4
Bit 4
Group diagnosis, module 5
Bit 5
Group diagnosis, module 6
Bit 6
Group diagnosis, module 7
Bit 7
Group diagnosis, module 8
Byte 3
Bit 0
Group diagnosis, module 9
Bit 1
Group diagnosis, module 10
Bit 2
Group diagnosis, module 11
Bit 3
Group diagnosis, module 12
Bit 4
Group diagnosis, module 13
Bit 5
Group diagnosis, module 14
Bit 6
Group diagnosis, module 15
Bit 7
Group diagnosis, module 16
PLC Configuration of the Valve System
Diagnostic type and device
Bus coupler diagnosis
Bus coupler diagnosis
Group diagnoses of modules
Group diagnoses of modules