AVENTICS | CANopen, CANopen sb | R412009415–BDL–001–AE
Commissioning and operation
Table 11:
S3, defining the monitoring threshold for valve voltage
Bit
Switch setting
3.1
OFF / ON (default)
3.2
OFF / ON (default)
3.3
OFF / ON (default)
3.4
OFF (default)
ON
3.5
OFF (default)
ON
3.6
OFF (default)/ON
3.7
OFF (default)/ON
3.8
OFF (default)/ON
2*
* Switch position
O
Activate or deactivate the diagnostic message to the
master with the S3.5 switch.
The modified switch position will only be activated
after a new "power on".
This setting can also be assigned using the Module
Control Object. If assigned via the Module Control
Object, the position of S3.5 will become ineffective.
The queued diagnoses are shown on the LEDs even if the
diagnostic message is turned off on the master.
7.1.4
The threshold 20.4 V/21.6 V can be adjusted for different
valve series (see Tab. 11 on page 84). In the delivery
condition, the threshold is set to 21.6 V (10 %) (S 3.4 set to
S4.4
OFF). If the supply voltage for the valve control drops
below this threshold, a diagnostic message will be
generated.
1*
S4.1
Function
Baud rate (see Tab. 10 on page 82)
Baud rate (see Tab. 10 on page 82)
Baud rate (see Tab. 10 on page 82)
Threshold for U
and U
Q1
Threshold for U
and U
Q1
Diagnostic message deactivated
Diagnostic message activated
NC
NC
NC
Switching the tolerance level for valve
supply U
and U
Q1
is 21.6 V (10 %)
Q2
is 20.4 V (15 %)
Q2
Q2