AVENTICS | CANopen, CANopen sb | R412009415–BDL–001–AE
During assembly
During commissioning
W
This device may only be used for industrial
applications (class A). An individual license must be
obtained from the authorities or an inspection center
for systems that are to be used in a residential area
(residential, business, and commercial areas).
W
Ensure that the power supply is within the stipulated
tolerance for the modules.
W
Observe the safety notes in the operating
instructions for your valve system.
W
A 24 V power pack supplies all components with
electricity. The power pack must be fitted with a safe
isolation in accordance with EN 60742, VDE 0551
classification. The corresponding electrical circuits
are thus SELV/PELV circuits in accordance with
IEC 60364-4-41.
W
Switch off the operating voltage before connecting
or removing the plugs.
W
The warranty only applies to the delivered
configuration. The warranty will not apply if the
product is incorrectly assembled.
W
Always make sure the relevant system component is
not under pressure or voltage before assembly or
disassembly. Ensure that the system is prevented
from power restoration during assembly work.
W
Ground the modules and valve system. Observe the
following standards when installing the system:
– DIN EN 50178, classification VDE 0160
– VDE 0100
W
Installation may only be performed in a voltage-free
and pressure-free state and only by a qualified
technician. In order to avoid accidents caused by
dangerous movements of the actuators, electrical
commissioning may only be carried out in a
pressure-free state.
W
Do not put the system into operation before it is
completely assembled as well as correctly wired
and configured, and after it has been tested.
W
The device is subject to the restrictions of the IP 65
protection class. Before commissioning, make sure
that all the connection seals and plugs are leaktight
to prevent fluids and foreign bodies from penetrating
the device.