Télécharger Imprimer la page

GE EntelliGuard G Manuel D'installation page 27

Publicité

1.3.4: Typical Connection Arrangement
1.3.4: Raccordement typique
1.3.4: Standaard aansluitwijze
Rondelles autobloquantes
Plain Washer (Heavy duty)
|
Veerring (Heavy duty)
Breaker type 'Automatic'
Switch Type
Disjoncteur
Interrupteur
Breaker type "automatisch"
Schakelaar type
--------------------------------------------------------------------------------------------------------------------------------------------------
GG04, S N & H
GJ04S & GW04N
GG04 E & M
GJ04H
GG07, S N & H
GJ07S & GW07N
GG07 E & M
GJ07H
GG08, S N & H
GJ08S & GW08N
GG08 E & M
GJ08H
GG10, S N & H
GJ10S & GW10N
GG10 E & M
GJ10H
GG13, S N & H
GJ13S & GW13N
GG13 E & M
GJ13H
GG16, S N & H
GJ16S & GW16N
GG16 E & M
GJ16H
GG20, S N & H
GJ20S & GW20N
GG20 E & M
GJ20H
GG25N, H & M
GJ25N & GW25H
GG32N, H & M
GJ32N & GW32H
GH32N, H & M
GK32N & GZ32H
GG32G & L
GJ32G
GG40N, H & M
GJ40N & GW40H
GH40N, H & M
GK40N & GZ40H
GG40G & L
GJ40G
GG50M & L
CJ50L
GG64M & L
CJ64L
Lock Washer
|
Sluitring
Customer bus
Customer bus
Rondelles
Envelope
In (A)
Taille
In (A)
Bouwgrootte
In(A)
1 or 2
400
1 or 2
400
1 or 2
630
1 or 2
630
1 or 2
800
1 or 2
800
1 or 2
1000
1 or 2
1000
1 or 2
1250
1 or 2
1250
1
1600
2
1600
1
2000
2
2000
2
2500
2 or 3
3200
2 or 3
3200
2 or 3
3200
2
4000
2
4000
3
4000
3
5000
3
6400
BREAKER
Hex Bolt (8.8)
Boulon hexagonal (8.8)
|
Hex bout (8.8)
Breaker terminal
Hex Nut (8.8)
Ecrou hexagonal (8.8)
|
Hex moer (8.8)
Recommended Copper Bus Bar sizes
Taille de barre cuivre recommendée
Aanbevolen koper bus bar formaat
1 x 40 x 10 or 1 x 80 x 5
or 2 x 40 x 5
1 x 40 x 10 or 1 x 80 x 5
or 2 x 40 x 5
1 x 50 x 10 or 1 x 100 x 5 or 2 x 50 x 5
1 x 50 x 10 or 1 x 100 x 5 or 2 x 50 x 5
1 x 50 x 10 or 1 x 100 x 5 or 2 x 50 x 5
1 x 50 x 10 or 1 x 100 x 5 or 2 x 50 x 5
1 x 60 x 10 or 2 x 60 x 5
1 x 60 x 10 or 2 x 60 x 5
2 x 40 x 10 or 2 x 80 x 5
2 x 40 x 10 or 2 x 80 x 5
2 x 50 x 10 or 2 x 100 x 5
2 x 50 x 10 or 2 x 100 x 5
3 x 50 x 10 or 3 x 100 x 5
3 x 50 x 10 or 3 x 100 x 5
4 x 50 x 10 or 4 x 100 x 5
4 x 100 x 10
4 x 100 x 10
4 x 100 x 10
4 x 100 x 10 + 1 x 100 x 5
4 x 100 x 10 + 1 x 100 x 5
4 x 100 x 10
5 x 120 x 10 or 6 x 100 x 10
7 x 120 x 10 or 8 x 100 x 10
EntelliGuard G
1
.3
Recommended Connection Cross
sections
The adjacent table indicates the
recommended bus bar dimensions
to be used in connecting the
EntelliGuard G™ Power Circuit
Breaker.
Le tableau adjacent indique les
tailles de barre cuivre
recommendées pour le
raccordement du disjoncteur de
puissance EntelliGuard GTM.
Aanbevolen aansluiting
doorsneden
De aangrenzende table geeft weer
wat de aanbevolen busbar maten
zijn om aan te sluiten op de
Entelliguard Gtm open vermogen
schakelaars.
1.3-05

Publicité

Chapitres

loading