Siemens simovert masterdrives CBP/CBP2 Mode D'emploi page 96

Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

05.2006
X480 - Digital inputs
and outputs
WARNING
X481 - Analog inputs
and outputs
Siemens AG
6SE7087-6NX84-0FF5
SIMOVERT MASTERDRIVES
The following connections are provided on the terminal strip:
♦ 3 digital inputs
♦ 4 bidirectional digital inputs/outputs
Terminal
Designation
38
M
39
P24ext.
40
DI1
41
DI2
42
DI3
43
DIO1
44
DIO2
45
DIO3
46
DIO4
Connectable cross-section: 1.5 mm² (AWG 16)
The ground cables are protected by a reactor.
Terminal 46 is at the top when installed.
Table 5-3
Terminal assignment at connection X480
The external 24 V supply must be sized for the currents of the digital
outputs.
There are the following connections on the terminal strip:
♦ 1 analog input with differential signal which can be used as a current
input and as a voltage input
♦ 2 analog inputs (single-ended), which can also be used as digital
inputs
♦ 2 analog outputs
Terminal
Designation
47
AO1
48
AO2
49
AOM
50
AI1P
51
AI1N
52
AI2
53
AI3
54
AIM
Connectable cross-section: 1.5 mm² (AWG 16)
The ground cables are protected by a reactor
Terminal 47 is at the top when installed.
Table 5-4
Terminal assignment at connection X481
Option boards
Significance
Ground digital
Ext. 24 V supply
Digital input 1
Digital input 2
Digital input 3
Digital input/output 1
Digital input/output 2
Digital input/output 3
Digital input/output 4
Significance
Analog output 1
Analog output 2
Ground analog output
Analog input 1 +
Analog input 1 -
Analog input 2
Analog input 3
Ground analog input
EB1 – Expansion Board 1
Range
0 V
+20 V ... +33 V
24 V, Ri = 4 kΩ
24 V, Ri = 4 kΩ
24 V, Ri = 4 kΩ
Input:
24 V, 4 kΩ
Output:
P24ext. - 2.5 V, 100 mA
Range
± 10 V, 5 mA
± 10 V, 5 mA
0 V
Voltage: ± 10 V, 40 kΩ
Current: ± 20 mA, 250 Ω
± 10 V, 40 kΩ
± 10 V, 40 kΩ
0 V