Displays; Start-Up - Siemens simovert masterdrives CBP/CBP2 Mode D'emploi

Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

05.2006
4.5

Displays

System connector
Operating display
Fault display
4.6

Start-up

NOTE
Siemens AG
6SE7087-6NX84-0FF5
SIMOVERT MASTERDRIVES
Three LED displays are provided on the front side of the SLB optional
board which give information on the current operating status.
These are as follows:
♦ SIMOLINK operating (green)
♦ Board operating (red)
♦ Data exchange with the basic unit (yellow)
Fixing screw
Fig. 4-5
SLB displays
LED
Status
Diagnostic information
Green
Flashing Fault-free net data transfer via SIMOLINK
Red
Flashing SLB operating
Yellow
Flashing Data exchange with basic unit is okay
Table 4-3
SLB operating display
LED
Status
Diagnostic information
Green
off/on
No net data exchange possible via SIMOLINK;
bus cable is not connected or is defective
Red
off
Voltage supply for SLB cut off;
replace SLB or basic unit
Yellow
off/on
No data exchange with the basic unit;
bus cable is not connected or is defective;
replace SLB or basic unit
Table 4-4
SLB fault display
After installation of the SLB optional board has been completed, an
automatic self-test is carried out when the basic unit (converter/inverter)
is powered up.
After this, the new board in the basic unit must be provided with a bus
address. Please refer to the documentation on the basic unit for further
details.
Please refer to the documentation of the respective basic unit regarding
instructions for the quick method of parameterization.
Option boards
SLB – SIMOLINK Board
Fixing screw
LED (green)
LED (red)
LED (yellow)
X470 external 24 V voltage supply
SIMOLINK output (light gray)
SIMOLINK input (dark gray)
4-7