05.2006
8.4

Connecting-up

Connecting-up
Encoder connection
13
25
14
1
Siemens AG
6SE7087-6NX84-0FF5
SIMOVERT MASTERDRIVES
SBR1/2 – Sensor Board Resolver (only for MASTERDRIVES Motion Control)
The optional board is provided with the following connections for the
signal cables:
♦ X414
Encoder connection via a 25-pole SUB D connector
♦ X410
Pulse encoder simulation via a 6-pole terminal strip
(only for SBR2)
Connect the shielded signal cables to the appropriate connection and
place the shield on the shield plate.
Connect the resolver to the optional board by means of the shielded
encoder cable. Use the pre-assembled cable for this purpose.
Connection is via a 25-pole SUB D connector on the front side of the
optional board.
Pin
3
Resolver output voltage sin+
4
Resolver output voltage sin-
5
Internal shield for 3 and 4
6
Resolver output voltage cos+
7
Resolver output voltage cos-
8
Internal shield for 6 and 7
9
Resolver excitation U
11
Ground for resolver excitation
13
Motor temperature sensing PTC/KTY
24
Internal shield for 13 and 25
25
Motor temperature sensing PTC/KTY
Housing
External shield
Table 8-2
Pin assignment at connection X414
Option boards
Significance
SS
Range
0 V to 7 V
automatic adaption,
5...10 kHz sine
8-5