Warning Messages - Wilo Stratos MAXO Notice De Montage

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

en
15.4

Warning messages

212
Faults, causes, remedies
Code
Fault
Voltage analogue input
overloaded.
410
Additional information about causes and remedy:
The fault impairs the binary inputs. EXT. OFF is set. The pump is stationary.
Motor or control module
faulty.
420
Additional information about causes and remedy:
The pump cannot determine which of the two components is faulty. Contact
service.
Control module faulty.
421
Additional information about causes and remedy:
Contact service.
Motor errors
449
Additional information about causes and remedy:
Motor error stops the pump. The cause of the fault is checked within few
seconds.
Table 47: Error messages
Warning displayed:
▪ The status display is marked in yellow.
▪ Warning message, warning code (W...), cause and remedy are described as text.
Display of a warning in 7-segment LED display:
▪ The warning is displayed with a red coloured warning code (H...).
Fig. 93: Warning code display
Warnings indicate restricted pump function. The pump continues to operate in re-
stricted mode (emergency operation).
Depending on the cause of the warning, emergency operation leads to a restriction
of the control function and even reactivation of a fixed speed.
If the pump identifies as part of permanent monitoring that the cause of the warn-
ing no longer applies, the warning is revoked and operation resumes.
If a warning message is output, the display is permanently on and the green LED indic-
ator is off.
Code
Fault
There is flow through
the pump in the oppos-
ite direction of flow.
550
Additional information about causes and remedy:
If flow passing through pump in the opposite direction is too strong, the mo-
tor can no longer start.
Undervoltage
551
Additional information about causes and remedy:
The pump is running. Undervoltage reduces the pump output.
If the voltage falls below 160 V, the reduced operation cannot be maintained.
Cause
Remedy
Voltage analogue in-
Check line and consumers
put short-circuited or
connected to power supply
too heavily loaded.
of analogue input for
short-circuit.
Motor or control
Replace motor and/or con-
module faulty.
trol module.
Control module
Replace the control mod-
faulty.
ule.
The pump is determ-
The pump provides in-
ining the exact cause
formation after few
of the fault.
seconds
about the cause of fault
and suitable countermeas-
ures.
Cause
Remedy
External influences
Check power control of the
cause flow against
pumps,
the direction of the
install non-return valve if
pump's flow.
needed.
Power supply has
Check power supply.
dropped below 195 V.
WILO SE 2018-11

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Stratos maxo-dStratos maxo-z

Table des Matières