Configuration point Selection / option
Hysteresis
0 to 99999
Window width
0 to 99999
Alarm delay on
0 to 999 s
Alarm delay off
0 to 999 s
alarm 2
Alarm type
Inactive
Min. alarm
Max.- alarm
alarm window
Alarm window invert.
Alarm / event list
OFF
Alarm
Event
Alarm text
Up to 20 characters of text
Threshold
-99999 to +99999
Hysteresis
0 to 99999
Window width
0 to 99999
Alarm delay on
0 to 999 s
Alarm delay off
0 to 999 s
Explanation
Distance to the threshold
Alarm on =
< Thresh. – Hyst. (With
minimum alarm)
> Thresh. + Hyst. (With max.
alarm)
Alarm OFF =
> Threshold (with minimum
alarm)
< Threshold (with max.
alarm)
Size of the alert window
(with alarm type "alarm
window") or of the window in
which no alarm is triggered
(with alarm type "inverted
alarm window")
Time delay between
occurrence of the alarm
condition and the alarm
turning on
Time delay between end of
the alarm set to on and the
alarm turning off
Choice of alarm type
OFF: No entry
Event: At the end of the
calibration interval, the text,
"Alarm Text" is written in the
event list.
Alarm: At the end of the
calibration interval, the text
"Alarm Text" is written in the
display list.
Text which is displayed
when an alarm is in the
display and/or is on the
event list.
Threshold at which an alarm
is triggered (depending on
the type of alarm)
Distance to the threshold
Alarm on =
< Thresh. – Hyst. (With
minimum alarm)
> Thresh. + Hyst. (With max.
alarm)
Alarm OFF =
> Threshold (with minimum
alarm)
< Threshold (with max.
alarm)
Size of the alert window
(with alarm type "alarm
window") or of the window in
which no alarm is triggered
( "inverted alarm window" in
the alarm type)
Time delay between
occurrence of the alarm
condition and the alarm
turning on
Time delay between end of
the alarm set to on and the
alarm turning off
157
Device menu
Default
0,00
0,00
0 sec
0 sec
Inactive
Alarm
Alarm 2
Temp.input 1
0,00
0
0
0 sec
0 sec
417102269 Rev. 2-08.2020