Fault elimination and messages
Errors and mes-
sages
Transmitter is
not supported
Transmitter
configuration
mismatch
HART® tunnel
open
HART® tunnel
open on other
port
Gas name mis-
match
Measurement
range maxi-
mum mismatch
Measurement
range minimum
mismatch
Measurement
range step mis-
match
Measurement
unit mismatch
Device assets
available
168
Cause
-
-
-
The connected HART
transmitter is not sup-
ported
-
-
-
The transmitter configu-
ration does not coincide
with the REGARD 3000
channel configuration
-
-
-
The HART
currently open on this
module port. Module
®
HART
functions are
not available
-
-
-
The HART
currently open on
another port in this
module. Module
HART® functions are
not available
-
-
-
Gas name configured in
channel does not match
gas name received by
transmitter
-
-
-
Maximum value config-
ured in channel does
not match maximum
value received by trans-
mitter
-
-
-
Minimum value config-
ured in channel does
not match minimum
value received by trans-
mitter
-
-
-
Measuring range step
configured in channel
does not match mea-
suring range step
received by transmitter
-
-
-
Measurement unit con-
figured in channel does
not match measure-
ment unit received by
transmitter
-
-
-
More device assets
available
Remedy
Select a supported
®
Dräger HART
mitter or disable trans-
mitter diagnostics
Use same configuration
for REGARD 3000
channel and transmitter
n/a
®
tunnel is
n/a
®
tunnel is
Use same configuration
for channel and trans-
mitter
Use same configuration
for channel and trans-
mitter
Use same configuration
for channel and trans-
mitter
Use same configuration
for channel and trans-
mitter
Use same configuration
for channel and trans-
mitter
Check channel assets
for further information
|
Instructions for use
REGARD 3000
®