Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

1
2
3
4
Contact assignment of the relevant Terminal Block on the Docking Station:
1
2
3
4
Technical data
Number of channels:
Current consumption
Gateway Module:
Power loss
Gateway Modul:
Bit rate:
Cable length fieldbus side:
Modbus RTU Gateway:
4.2.4

Slotcover

Slotcover for assigning unused slots in a Docking Station.
|
Instructions for use
REGARD 3000
Bus State (Modbus)
Is illuminated if a fieldbus master is connected and actively communicating.
Is not illuminated if the fieldbus master does not actively communicate for
more than 1 s.
Fault display
Lights if there is a module or channel error.
Lights green if valid communication with the fieldbus-specific gateway is tak-
ing place.
Data transfer display
Flashes when the module is communicating.
B data -
A data +
RS485 GND
Shield
1 channel, bidirectional. A Gateway Module always
occupies one port in the total system.
Typ. 100 mA at 24 V
Max. 4 W at 24 V
Adjustable: 9,600 to 921,600 Baud
<57,600 baud max. 1200 m
<230,400 Baud max. 500 m
<921,600 baud max. 120 m
System components
1
2
3
4
|
en
115

Publicité

Table des Matières
loading

Table des Matières