7.3 System behaviour

7.3.1 System behaviour based on 4 to 20 mA signals

The following table describes the system behaviour in the various input signal areas.
0 mA to
0.1 mA
Measured
Display
value display
System infor-
mation display 4-20 mA sig-
nal fault
Gateway Mod-
2)
NaN
ule measured
value output
Gateway Mod-
Error in the
ule system
notification
information
and confirma-
tion register
Relay config-
Last switching
ured to alarms
status is
3)
retained
Relay config-
Fault relay
ured to spe-
activated,
cial signals
other relays
retain the last
switching state
0.1 mA to
Underrange
minimum to
Underrange
minimum
Underrange
maximum
Current mea-
Display
sured value
,
,
,
Under range
1)
Current mea-
2)
NaN
sured value
Error, warn-
None
ing, informa-
tion, Inhibit in
the notifica-
tion and confir-
mation
1)
register
Last switching
Switching as
status is
per configura-
tion
3)
retained
Depending on
Information
the system
relay acti-
configuration
vated, no input
signal-depen-
dent switching
action in the
other relays
Underrange
4 mA to
maximum to
20 mA
4 mA
Current mea-
Current mea-
sured value
sured value
None
None
Current mea-
Current mea-
sured value
sured value
None
None
Switching as
Switching as
per configura-
per configura-
tion
tion
No input sig-
No input sig-
nal-depen-
nal-depen-
dent switching
dent switching
action
action
20 mA to
Overrange
minimum to
Overrange
minimum
Overrange
maximum
Current mea-
Display
sured value
None
Over range
Current mea-
Current mea-
sured value
sured value
None
Over range
notification in
the notifica-
tion and confir-
mation register
Switching as
Switching as
per configura-
per configura-
tion
tion
No input sig-
Information
nal-depen-
relay acti-
dent switching
vated, no input
action
signal-depen-
dent switching
action in the
other relays
Overrange
maximum to
38 mA
Display
Measure-
ment signal
fault
2)
NaN
Error in the
notification
and confirma-
tion register
Last switching
status is
3)
retained
Fault relay
activated,
other relays
retain the last
switching state