Installation and commissioning
U
Tmin
U
V
The following points only apply for installation in a cabinet:
– The REGARD 3000 system and the system components must be protected from
unauthorised access (e.g. with a lockable cabinet).
– Supplying the REGARD 3000 with voltage from a DC mains is not permitted.
– Use one of the following power supply units to supply power to the REGARD
3000 from the AC mains supply:
– SELV power supply unit (separated or safety extra low voltage) pursuant to
– PELV power supply unit (protective extra low voltage) pursuant to IEC 61140
– When selecting the type of power supply unit (SELV or PELV), pay attention to
the requirements of the connected devices.
– Dräger recommends SELV power supply units for larger systems with earth
potential subject to faults.
– Dräger recommends protecting the outputs of the power supply units used
against overload.
– If necessary, install adequate active cooling in the switch cabinet to protect the
components in the switch cabinet from overheating.
120
Minimum voltage for the operation of the transmitter in accordance with the
instructions for use
Voltage present on the input of the REGARD (nominally 18 V DC to
30 V DC)
IEC 60950-1
|
Instructions for use
REGARD 3000