Updating The Display Unit Firmware; Fault Elimination And Messages; General - Dräger REGARD 3000 Mode D'emploi

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

|
en

Fault elimination and messages

8.6.3

Updating the Display Unit firmware

This function can be used to update the Display Unit firmware. During the update,
no channel display is available on the Display Unit , but the REGARD 3000 system
remains operational.
CAUTION
Damage to the Display Unit
An unexpected interruption during the update (e.g. due to a power cut) may result in
the Display Unit ceasing to function.
► Follow the directions of the update wizard.
Prerequisite:
– A USB stick with the new firmware is available.
The USB stick must be formatted with FAT32.
Contact Dräger Service for the current firmware.
1. Select
 The update wizard is started.
2. Plug a USB stick with the new firmware into the USB port of the Display Unit.
3. Follow the directions of the wizard.
9
Fault elimination and messages
9.1

General

The system behaviour and the relevant outputs for the light ring and horn are
described in a separate chapter (see "Light ring display and horn sound",
page 140).
Errors and mes-
sages
Received own
module address
Coil current
fault
Received own
module location
Special state
relay fault
Docking Sta-
tion alarm relay
fault
164
> Update.
Cause
x
x
-
Module fault, duplicate
MAC address
x
x
-
Module error, coil cur-
rent is outside the
expected range
x
x
-
Error in the Docking
Station, incorrect serial
number or slot
x
x
-
Error in the Docking
Station, special state
relay not switching
x
x
-
Error in the Docking
Station, alarm relay not
switching
Remedy
Replace affected mod-
ule
Replace affected mod-
ule
Replace affected Dock-
ing Station
Replace affected Dock-
ing Station
Replace affected Dock-
ing Station
|
Instructions for use
REGARD 3000

Publicité

Table des Matières
loading

Table des Matières