Power Connections Of E82Ev153K4B; Mains Connection; Fuses And Cable Cross-Sections - Lenze Global Drive 8200 vector Instructions De Montage

Masquer les pouces Voir aussi pour Global Drive 8200 vector:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Electrical installation
Power connections E82EV153K4B ... E82EV303K4B
5.2
Power connections of E82EV153K4B ... E82EV303K4B
5.2.1

Mains connection

Connection with mains choke
Connection with subassembled mains filter
Connection with built-on assembled mains filter

Fuses and cable cross-sections

Type
mains
1)
E82EV153K4B2x1
3/PE AC 320 V -0 % ... 550 V +0 %
2)
E82EV153K4B2x1
45 Hz -0 % ... 65 Hz +0 %
2)
E82EV223K4B2x1
DC 450 V -0 % ... 775 V +0 %
2)
E82EV303K4B2x1
1)
Without mains choke
2)
With mains choke
Observe national and regional regulations (e. g. VDE 0113, EN 60204)
Please observe the following when using e.l.c.bs.:
E.l.c.bs must only be installed between mains supply and controller.
Earth leakage circuit breakers can be activated although not required by
– capacitive compensating currents of the cable shields during operation (especially with long,
shielded motor cables),
– simultaneous connection of several controllers to the mains supply,
– use of additional RFI filters.
78
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
Connection brake chopper (  Operating Instructions for the brake chopper )
Connection mains filter temperature monitoring with PTC thermistor
Z1 Mains choke/mains filter
Installation to EN 60204-1
Fuse
L1, L2, L3, PE [mm
M63 A
25
M35 A
10
M50 A
16
M80 A
25
3)
Use UL-approved cables, fuses and fuse holders only.
UL fuse: 500 ... 600 V, tripping characteristic "H", "K5" or "CC"
4)
All-current sensitive e.l.c.b.
EDK82EV903 DE/EN/FR 2.2
3)
Installation to UL
2
]
Fuse
L1, L2, L3, PE [AWG]
63 A
4
35 A
8
50 A
6
80 A
3
8200vec288
4)
FI
≥300 mA
L