Commissioning - 8200 vector without function module
•
The 8200 vector can only be used when the FIF cover is mounted!
– If the FIF cover is not mounted, the 8200 vector is inhibited (keypad:
•
Since the 8200 vector without function module does not have any control terminals, starting and stopping during operation is also
possible via switching the mains.
– For cyclic switching: Observe break times of 3 minutes!
•
Function
stores the setpoint at the time when operation is interrupted by switching the mains or mains failures. The drive
restarts automatically as soon as the mains connection is built up again.
•
If the drive does not start at step
Step
Plug in the keypad
Switch on the mains voltage.
Self start possible!
Select the setpoint via the function
.
Any faults or errors during commissioning or operation?
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
(
is not off), press
Note
The keypad is not included in the delivery package.
The controller is ready for operation after approx. 1 second.
Keypad:
activate
is off. The drive should be running now.
CW rotation:
Display indicates output frequency.
CCW rotation
! It is under the dummy cap
(Delivery status).
).
to enable the 8200 vector.
8200vec271
see chapter
8
"Commissioning"
9
" Fault recognition and
elimination"