Lenze Global Drive 8200 vector Instructions De Montage page 111

Masquer les pouces Voir aussi pour Global Drive 8200 vector:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Troubleshooting and fault elimination
Error messages
1)
Keypad
PC
Error
75
Faulty parameter transfer when
Pr
using the keypad
72
Wrong PAR1 transfer when
Pr1
using the keypad.
73
Wrong PAR2 transfer when
Pr2
using the keypad.
77
Wrong PAR3 transfer when
Pr3
using the keypad.
78
Wrong PAR4 transfer when
Pr4
using the keypad.
79
Internal fault
Pr5
81
Time fault during parameter
Pt5
set transfer
76
Faulty auto-TRIP reset
rSt
85
Wire breakage analog input 1
sd5
87
Wire breakage analog input 2
sd7
1)
LECOM-fault number, display in parameter setting program Global Drive Control (GDC)
110
EDK82EV903 DE/EN/FR 2.2
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
Cause
All parameter sets are defective
PAR1 is defective.
PAR2 is defective.
PAR3 is defective
PAR4 is defective
EEPROM is defective
Data flow from keypad or PC interrupted, e. g.
keypad was disconnected during transfer
More than 8 fault messages in 10 minutes
Current at analog input < 4 mA at setpoint range
4 ... 20 mA
Remedy
It is absolutely necessary to repeat the data transfer or
load the Lenze setting before enabling the controller.
Contact Lenze
It is absolutely necessary to repeat the data transfer or
load the Lenze setting before enabling the controller.
Depends on the error message
Close circuit at analog input
L

Publicité

Table des Matières
loading