Ecolab EcoAdd Manuel D'utilisation page 290

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Control / Software
Step 2: [Operating mode] - [Current] - setting:
2
10
Fig. 41: Operating mode: Current
1.
[Call up the main menu] :
2.
[Operating mode] - [Current] .
3.
[ Click Next]
ð Screen change for the Current setting.
4.
'Select the current range' :
n
0 to 20 mA (< 0.2 mA = 0 % metering capacity, > 19.8 mA = 100 % metering
capacity)
n
4 to 20 mA (< 4.2 mA = 0 % metering capacity, > 19.8 mA = 100 % metering
capacity)
n
20 to 4 mA (> 19.8 mA = 0 % metering capacity, < 4.2 mA = 100 % metering
capacity)
n
20 to 0 mA (> 19.8 mA = 0 % metering capacity, < 4.2 mA = 100 % metering
capacity)
5.
Press the button
ð Screen change for setting the min. metering capacity.
6.
'mA' in the place before the decimal point using the scrollbar.
Lower setting value + 0.2 mA = 0 % metering capacity
Upper setting value - 0.2 mA = 100 % metering capacity
7.
Select the field for entering the value after the decimal point.
ð The colour changes to dark blue, which indicates that the field is ready for input.
8.
Set the decimal point with the scrollbar.
9.
Press the button
ð Screen change for setting the max. metering capacity.
10.
'mA' in the place before the decimal point using the scrollbar.
11. Select the field for entering the value after the decimal point.
ð The colour changes to dark blue, which indicates that the field is ready for input.
12. Set the decimal point with the scrollbar.
13. Press the
ð Save settings, change screen: [Current].
14. Press the
15. By pressing the
16. By pressing the
417102276 Rev. 5-02.2020
3
4
13
11
12
Ä Chapter 7.7 'Main menu' on page 73
to save the setting.
Next.
Next.
button.
button to return to the menu: [Operating mode].
button, you can return to the [Call up the main menu].
button, you can return to the [operating display].
5
6
14
88
9
8
7
15