Commissioning
Menu no.
5.59
Description
Collective fault signal (SSM) function
Value range
fall, raise
Factory setting
raise
"fall": The relay drops out. This function can be used to
Explanation
monitor the mains voltage supply.
"raise": The relay picks up.
Menu no.
5.60
Description
Pump cycling
Value range
on, off
Factory setting
on
Menu no.
5.61 (Control ECe-Booster only)
Description
Zero-flow test
Value range
on, off
Factory setting
on
Menu no.
5.62
Description
Dry-running protection: Switch-off time delay
Value range
0 ... 180 s
Factory setting
15 s
Menu no.
5.63
Description
Dry-running protection: Reactivation time delay
Value range
0 ... 1800 s
Factory setting
10 s
Menu no.
5.68 (Control EC-Booster only)
Description
Mains connection rotating field monitoring On/Off
Value range
on, off
Factory setting
on
NOTICE! Switch off during alternating current connection!
Menu no.
5.69 (Control EC-Booster only)
Description
Motor current monitoring On/Off
Value range
on, off
Factory setting
on
NOTICE! Switch off during alternating current connection!
WILO SE 2019-07