6.5.2
Overview of components: Wilo-
Control ECe-Booster
1
7
5
9
6
10
4
Fig. 4: Control ECe-B 2...
7
Current Pump1
9
A(+) B(-) GND
4
23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40
6
41 42 43 44 45 46 47 48 49 50 51 52 53 54
4
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22
L1 L2 L3 (N)
3
PE
1
3
5
1
3
5
1
3
5
2
4
6
2
4
6
2
4
Fig. 5: Control ECe-B 3...
6.5.3
Switchgear mains connection:
Control EC-Booster
Installation and operating instructions Wilo-Control EC/ECe-Booster
Installation
1
3
3
4
5
6
7
9
10
1
Current Pump2
Current Pump3
3
4
4
55
56 57
58
59
60 61
62
63
64
65
66
67
68
5
6
10
J4
J2
J3
7
5
1
9
1L1
3L2
5L3
1 ON
1
0
OFF
10
2T1
4T2
6T3
6
2
3
DANGER
Risk of fatal injury due to electrical current when the main switch is
switched off!
Even when the main switch is switched off, there is mains voltage power to the
voltage selection terminal. There is a risk of fatal injury! Make the voltage selection
before connecting the product to the mains.
CAUTION
Material damage due to incorrectly set mains voltage!
The switchgear can be operated at different mains voltages. The mains voltage is set
to 400 V at the factory. To use another mains voltage, change the position of the
cable jumper before connection. If the wrong mains voltage is set, the switchgear
will be destroyed!
Insert the connection cable laid by the customer through the threaded cable glands and
secure. Connect the wires to the terminal strip according to the connection diagram.
Main switch/mains connection
Terminal strip: Earth (PE)
Terminal strip: Controls/sensors
Circuit breaker
Output relay
Control board
ModBus RTU: RS485 interface
ModBus RTU: Jumper for termination/polarisation
Main switch/mains connection
Terminal strip: Earth (PE)
Terminal strip: Controls/sensors
Circuit breaker
Output relay
Control board
ModBus RTU: RS485 interface
ModBus RTU: Jumper for termination/polarisation