Wilo Control EC-Booster Notice De Montage Et De Mise En Service page 71

Masquer les pouces Voir aussi pour Control EC-Booster:
Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 89
Fig. 38: Menu 5.43
Fig. 39: Menu 5.45
Fig. 40: Menu 5.46
Fig. 41: Menu 5.47
Fig. 42: Menu 5.48
Fig. 43: Menu 5.49
Fig. 44: Menu 5.58
Installation and operating instructions Wilo-Control EC/ECe-Booster
Commissioning
Menu no.
5.43
Description
"Pump kick" running time
Value range
0 ... 60 s
Factory setting
5 s
Menu no.
5.45
Behaviour during sensor fault – number of pumps to be
Description
switched on
Value range
0 ... 3*
Factory setting
0
* Maximum value dependent on number of pumps set
Explanation
(Menu 5.02).
Menu no.
5.46 (Control ECe-Booster only)
Description
Minimum speed of the pumps
Value range
0 ... 50 %
Factory setting
30 %
Menu no.
5.47 (Control ECe-Booster only)
Description
Maximum pump speed
Value range
80 ... 100 %
Factory setting
100 %
Menu no.
5.48 (Control ECe-Booster only)
Description
Acceleration ramp for frequency converter
Value range
0 ... 10 s
Factory setting
3 s
Menu no.
5.49 (Control ECe-Booster only)
Description
Deceleration ramp for frequency converter
Value range
0 ... 10 s
Factory setting
3 s
Menu no.
5.58
Description
Collective run signal (SBM) function
Value range
on, run
Factory setting
run
"on": switchgear ready for operation
Explanation
"Run": At least one pump is running.
en
71

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Control ece-booster

Table des Matières