8.3

Start initial configuration

1
2
3
5
7
Fig. 27: Enable parameter input
Fig. 28: Menu 5.01
Fig. 29: Menu 5.02
Fig. 30: Menu 5.03
Installation and operating instructions Wilo-Control EC/ECe-Booster
Commissioning
Observe the following points during the configuration:
▪ If there is no input or operation for 6 minutes:
– the display illumination is switched off.
– the display returns to the main screen.
– parameter input is locked.
▪ Some settings can only be adjusted when there is no pump in operation.
▪ The menu is automatically adapted based on the settings. Example: The Menus 5.41 ...
5.43 are only visible when the "pump kick" function (Menu 5.40) is activated.
▪ The menu structure is valid for all EC switchgears (e.g. HVAC, Booster, Lift, Fire, etc.).
This may lead to gaps in the menu structure.
As standard, the values are only displayed. To change the values, the parameter input in
Menu 7.01 must be enabled:
1. Press the operating button for 3 s.
⇒ Menu item 1.00 appears
2. Turn the operating button until menu 7 appears.
3. Press the operating button.
⇒ Menu 7.01 appears.
4. Press the operating button.
5. Change the value to "on": Turn the operating button.
6. Save value: Press the operating button.
⇒ The menu is enabled and can be changed.
7. Turn the operating button until the end of menu 7 appears.
8. Press the operating button.
⇒ Back to the main menu level.
▶ Start initial configuration:
- Menu 5: Basic settings
- Menu 1: Switch-on/off values
- Menu 2: Field bus connection (if available)
- Menu 3: Enable pumps
Menu 5: Basic settings
Menu no.
Description
Factory setting
Menu no.
Description
Value range
Factory setting
Menu no.
Description
Value range
Factory setting
5.01
Control mode
Constant pressure control (p-c)
5.02
Number of connected pumps
1 ... 3
3
5.03
Standby pump
on, off
off
en
69