no
Holding register
Name
(Protocol)
40062
Switch box state
(61)
Error state
40139 - 40140
(138-139)
40141
Acknowledge
(140)
40142
Alarm history index
(141)
40143
Alarm history error
(142)
code
648
Vedlegg
Data type
Scale & unit
BITMAP
BITMAP32
BOOL
UINT16
UINT16
0.1
Forklaring
* R = kun lesetilgang, RW = lese- og skrivetilgang
Elements
Access*
0: SBM
R
1: SSM
0: Sensor error
R
1: P max
2: P min
3: FC
4: TLS
5: Pump 1 Alarm
6: Pump 2 Alarm
7: Pump 3 Alarm
8: Pump 4 Alarm
9: Pump 5 Alarm
10: Pump 6
Alarm
11: -
12: -
13: Frost
14: Battery Low
15: High water
16: Priority off
17: Redundancy
18: Plausibility
19: Slave
communication
20: Net supply
21: Leakage
W
RW
R
Added
31.000
31.000
31.000
31.000
31.000
WILO SE 2019-07