Fe Connection; Profinet-Io Fieldbus Interface - Aventics PROFINET-IO Mode D'emploi

Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 117
86
AVENTICS | PROFINET-IO | R412015162–BDL–001–AE
Assembly
PO WE R
X10
2
1
3
4
1
Table 15:
Pin
1
2
3
4
5.3.8
O
To discharge EMC interferences, connect the FE
2
connection (2) on the left EP end plate of the VS via a low-
impedance line with a functional grounding.
Recommended cable cross-section: 10 mm
Total current is too high
Every output is supplied with a continuous current of max. 0.5 A.
Current loads over 0.5 A per output can damage the system.
O
Make sure that the current load of 0.5 A per output is not
exceeded.
With an HF04-/HF04XF valve block, connect the FE connection (1)
on the valve block to the functional grounding via a low-
impedance line.
5.4
Type
Potential separation
Station address
Baud rate
The bus coupler can be operated on a PROFINET-IO fieldbus
with real-time classes RT and IRT.
Load supply assignment for 8x output module, 8DO, M12x1,
A-coded
X10
Assignment
Free
GND reference for power supply 2
0x
24 V supply voltage 1 for outputs O0 to O3
GND
GND reference for power supply 1
24 V supply voltage 2 for outputs O4 to O7

FE connection

NOTICE

PROFINET-IO fieldbus interface

Ethernet
Yes
Any in acc. with RFC specifications
100 MBaud
2
.

Publicité

Table des Matières
loading

Table des Matières