Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 117
AVENTICS | PROFINET-IO | R412015162–BDL–001–AE
6.3.2

System error

The following errors can be detected by the device.
-
Table 23:
System error
Error
Description
SREG
Internal communication has
malfunctioned.
W
An internal processing error
has occurred or the
subordinate SPI
communication has failed
W
Initialization of the SREG has
failed
SPI
SPI communication has failed:
W
Internal SPI error
(communication
malfunctioning)
W
SPI timeout (communication
interrupted)
APPL
The detected configuration
(connected I/O modules) contains
unknown IDs
SYSTEM
An internal system error has
occurred
INIT
The system cannot be started,
self-test has failed
Commissioning and Operation
Reaction
W
Set the PN
diagnostic alarm
"System Error"
W
Set the diagnostic
LED
W
Set the PN
diagnostic alarm
"System Error"
W
Set the diagnostic
LED
W
Set the PN
diagnostic alarm
"System Error"
W
Set the diagnostic
LED
W
Set the PN
diagnostic alarm
"System Error"
W
Set the diagnostic
LED
W
Reset
101

Publicité

Table des Matières
loading

Table des Matières