ero electronic FKS-MK1 Manuel De Service page 90

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

d) when the "P52" parameter is set to "Undr"
d.1) when an UNDERRANGE condition is detected, the
output power will be forced to the safety value set in
parameter "P53".
d.2) if an overrange condition is detected the instrument will
operate as described at point a.1).
P 5 3
P 5 3
P 5 3
P 5 3
P 5 3
Safety value applied at the output
Safety value applied at the output
Safety value applied at the output
Safety value applied at the output
Safety value applied at the output
This parameter is available if at least one control output is configured
and if "P52" is configured as "Ov.Un", "OvEr" or "Undr".
Range:
- From 0 to 100 if the instrument is configured with one
control output.
- From -100 to 100 if the instrument is configured with
two control outputs.
N O T E :
N O T E :
N O T E :
N O T E :
N O T E :
- When the instrument is configured with two control outputs,
the value of "P53" is the result of the following relation:
"P53" = Out1-Out2.
P 5 4
P 5 4
P 5 4
P 5 4
P 5 4
Antireset windup
Antireset windup
Antireset windup
Antireset windup
Antireset windup
This parameter is available when at least one control output is
configured.
Range: from 10% to 200%.
Maximum speed of variation of the
Maximum speed of variation of the
Maximum speed of variation of the
Maximum speed of variation of the
Maximum speed of variation of the
P 5 5
P 5 5
P 5 5
P 5 5
P 5 5
control output
control output
control output
control output
control output
This parameter is available when at least one control output is
configured.
Range: from 1%/s to 25%/s.
Above this value, the display shows "InF" and the limitation is
disabled.
N O T E :
N O T E :
N O T E :
N O T E :
N O T E :
- this function will also be active if the instrument is configured for
ON/OFF control.
fks-MK1-B1-A0.pmd
2
P 5 6
P 5 6
P 5 6
P 5 6
P 5 6
"Loop Break Alarm" (LBA) function
"Loop Break Alarm" (LBA) function
"Loop Break Alarm" (LBA) function
"Loop Break Alarm" (LBA) function
"Loop Break Alarm" (LBA) function
This parameter is available when at least one control output is
configured.
Range:
nonE = function disabled
diSP = function enabled. The alarm is only signalled
on the display
Out2 = function enabled. Output 2 is used as output
for the LBA alarm.
N O T E :
N O T E :
N O T E :
N O T E :
N O T E :
a) The selection "Out2" is only available if "P10" is different from
"CooL".
b) Setting "P10" equal to "CooL" when P56 is equal to "Out2",
"P56" is forced to "dISP".
c) If output 2 is set as fault alarm or Alarm 2, the LBA state is put
in "or".
d) The LBA function is described in section 1.4.
P57
P57
P57
P57
P57
"Loop Break Alarm" (LBA) threshold
This parameter is available when at least one control output
is configured and "P56" is different from "nonE".
Range: from 0 to 500 digit
P 5 8
P 5 8
P 5 8
P 5 8
P 5 8
"Loop Break Alarm" (LBA) time
"Loop Break Alarm" (LBA) time
"Loop Break Alarm" (LBA) time
"Loop Break Alarm" (LBA) time
"Loop Break Alarm" (LBA) time
This parameter is available when at least one control output is
configured and "P56" is different from "nonE".
Range: from 00.01 to 40.00 mm.ss (minutes/seconds)
P 5 9
P 5 9
P 5 9
P 5 9
P 5 9
"Loop Break Alarm" (LBA) hysteresis
"Loop Break Alarm" (LBA) hysteresis
"Loop Break Alarm" (LBA) hysteresis
"Loop Break Alarm" (LBA) hysteresis
"Loop Break Alarm" (LBA) hysteresis
This parameter is available when at least one control output is
configured and "P56" is different from "nonE".
Range: from 1 to 50% of the output power
B.2
09/05/2006, 10.06