Hysteresis (for ON/OFF check
Hysteresis (for ON/OFF check
Hysteresis (for ON/OFF check
Hysteresis (for ON/OFF check
Hysteresis (for ON/OFF check) ) ) ) )
This parameter is available when at least one control output is
configured and Pb =0 (check On/OFF)
Range: from 0.1% to 10.0% of the input span ("P3" / "P4").
t i
t i
t i
t i
t i

Integral time

Integral time
Integral time
Integral time
Integral time
This parameter is available when at least one control output is
configured and Pb is different from 0.
Range:
from 00.01 to 20.00 mm.ss
Beyond this value the display goes dark (with the
exception of the decimal point) and the integral action is
excluded.
N O T E :
N O T E :
N O T E :
N O T E :
N O T E :
- When the instrument uses the SMART algorithm, the value of
"ti" will be limited as selected by parameters "P64" and "P65"
(see "Advanced configuration parameters").
t d
t d
t d
t d
t d
Derivative action time e e e e
Derivative action tim
Derivative action tim
Derivative action tim
Derivative action tim
This parameter is available when at least one control output is
configured, "P15" is equal to "Pid" and "Pb" is different from 0.
Range: From 00.00 to 10.00 mm.ss
N O T E :
N O T E :
N O T E :
N O T E :
N O T E :
When the instrument uses the SMART algorithm, "td" will be
proportional to the value of "ti", in agreement with what was
calculated by TUNE
fks-MK1-1-A0.pmd
15
I P
I P
I P
I P
I P
Pre-load of the integral action
Pre-load of the integral action
Pre-load of the integral action
Pre-load of the integral action
Pre-load of the integral action
This parameter is available when at least one control output is
configured and Pb is different from 0.
Range:
-
from 0 to 100 % of the output when the instrument is
configured with one control output.
-
from -100 to 100 % of the output when the instrument is
configured with two control outputs.
C C C C C
Main output cycle time
Main output cycle time
Main output cycle time
Main output cycle time
Main output cycle time
This parameter is available if output 1 is configured as control
output.
Range: from 1 to 200 sec.
C 2
C 2
C 2
C 2
C 2
Secondary output cycle time e e e e
Secondary output cycle tim
Secondary output cycle tim
Secondary output cycle tim
Secondary output cycle tim
This parameter is available if output 2 is configured as control
output.
Range: from 1 to 200 sec.
r C
r C
r C
r C
r C
Second output relative gain
Second output relative gain. . . . .
Second output relative gain
Second output relative gain
Second output relative gain
This parameter is available if output 2 is configured as control
output.
Range: from 0.20 to 1.00
N O T E
N O T E
N O T E :
N O T E
N O T E
- When the instrument uses the SMART algorithm and "P66"=
ON, the value of rC is limited in relation to the type of cooling
media used ("P11", see sect. 5.2):
0.85 - 1.00 if air
0.80 - 0,90 if oil
0.30 - 0.60 if water
GB
15
09/05/2006, 15.06