16 = TC type
S range
-60 /
17 = TC type
R range
0 /
18 = TC type
B range
32 /
19 = TC type
W5 range
0 /
* 20 = RTD Pt100
range
-330 /
21 = Linear
range
0 /
22 = Linear
range
12 /
* For these ranges it is possible to select a readout with one
decimal figure, in this case the instrument cannot display a
measure lower than -199.9 or higher than 999.9 and the input
range will be limited by it.
N O T E
N O T E
N O T E
N O T E :
N O T E
If the type of input is modified, the instrument will automatically
force:
- parameter "P3" to the new initial scale value (0 for linear
inputs),
- parameter "P4" to the new full scale value (4000 for linear
inputs),
- parameter "P16" to the new initial scale value,
- parameter "P2" to "no decimal figure".
P 2
P 2
P 2
P 2
P 2
Decimal point position
Decimal point position
Decimal point position
Decimal point position
Decimal point position
This parameter is only available for the inputs from 1 to 4, 10
and 20 and linear inputs 21 and 22.
----.
= No decimal figure.
---.-
= One decimal figure.
--.--
= Two decimal figures.
-.---
= Three decimal figures.
N O T E S
N O T E S :
N O T E S
N O T E S
N O T E S
a) For the inputs from 1 to 4, 10 and 20, it is possible to
select a readout with one decimal figure, in this case the
instrument cannot display a measure lower than -199.9 or
higher than 999.9 and the input range will be limited by it.
For this inputs, a chance of the decimal point position will
be considered as a change of the type of input.
b) For the linear inputs (21 and 22) all the positions are available.
fks-MK1-1-A0.pmd
7
+3200 °F
P 3
P 3
P 3
P 3
P 3
+3200 °F
Readout - initial scale value
Readout - initial scale value
Readout - initial scale value
Readout - initial scale value
Readout - initial scale value
+3300 °F
+4170 °F
Range:
+1560 °F
- For linear inputs it is programmable from -1999 to 9999.
60 mV
- For TC and RTD inputs it is programmable from the
60 mV
minimum value of the measurement range to "P4" (full
scale value).
NOTES:If the value of this parameter is changed,
NOTES
NOTES
NOTES
NOTES
a) Parameter "rL" will be aligned to the new value of "P3";
b) Parameter "rH" will be checked and, if out of range, it will be
aligned to the value of "P4";
c) If a linear input has been selected, the value of "P16" will be
aligned to the value of "P3".
d) Parameters SP/AL1/AL2 (if process alarms) will be
checked and, if out of range, will be aligned to the new
value of "P3.
P 4
P 4
P 4
P 4
P 4
Readout - full scale value
Readout - full scale value
Readout - full scale value
Readout - full scale value
Readout - full scale value
Ranges:
- For linear inputs it is programmable from -1999 to 999.
- for inputs TC/RTD it is programmable from initial scale
value (P3) to the maximum value of the measurement
range.
N O T E S
N O T E S
N O T E S
N O T E S :
N O T E S
a) If the value of this parameter is changed,
a.1) Parameter "rL" will be aligned to the new value of
"P3";
a.2) Parameter "rH" will be checked and, if out of range, it
will be aligned to the value of "P4";
a.3) If a linear input has been selected, the value of "P16"
will be aligned to the value of "P3".
a.4) Parameters SP/AL1/AL2 (if process alarms) will be
checked and, if out of range, will be aligned to the new
value of "P3.
B) The span ("P4" - "P3"), in absolute value, must be greater
than:
- 300°C (550°F) for inputs TC
- 100°C (200°F) for inputs RTD
- 100 digits for linear inputs
GB
7
09/05/2006, 15.06